Open-cell vs closed-cell spray foam in an attic

By Insulation Report Editorial. Last reviewed August 2026. How we research this.

Open-cell spray foam runs about R-3.5 to R-3.7 per inch and closed-cell about R-6.0 to R-7.0, so R-49 takes roughly 13.2 to 14 inches of open-cell against 7 to 8.2 inches of closed-cell. Closed-cell also cures rigid and acts as its own vapour retarder. Open-cell stays soft and vapour-open. Both air seal, both are contractor-installed two-part chemistry, and neither is a do-it-yourself job at attic scale. The choice between them matters less than a decision most homeowners are never asked to make: whether the insulation goes on the attic floor or on the underside of the roof deck. Foam at the roofline turns a vented attic into a conditioned one, which normally means closing the vents and changing how the roof dries. That is a building-science decision, not a material preference. On an ordinary vented attic with a reachable floor, loose-fill is far cheaper and does the same job.

Every attic material is compared against every other one on the insulation types hub, which carries the master table. Below are only the two spray foams, and the decision that outranks the choice between them: whether the insulation belongs on the attic floor or under the roof deck.

The one-line answer, and who each foam is for

Closed-cell where depth is the constraint or the assembly needs vapour control at the roof deck. Open-cell where there is room for the thickness and the assembly can tolerate a vapour-open layer. Neither one on an ordinary vented attic floor.

Open-cell spray polyurethane foam expands into a soft, low-density layer with cells that connect to each other. That structure is why it is vapour-open, why water runs through it, why it absorbs airborne sound better than its sibling, and why it costs less per inch: less chemical goes into the same volume. It is the usual choice at the roofline in mild and hot climates, where the sheathing has a drying path and the vapour openness is not working against you.

Closed-cell spray polyurethane foam cures dense and rigid with sealed cells. It carries the highest R per inch of any material this site tracks, acts as its own vapour retarder at ordinary installed thickness, resists liquid water, and stiffens the assembly it is sprayed into. It is the choice where the inches are not available, where the code path for an unvented attic asks for air-impermeable insulation directly against the deck, and in the tight triangle at the eaves where nothing else fits.

Side by side

The thermal half of the comparison is arithmetic, so it is worth doing exactly rather than describing. The R-value targets used here are the ENERGY STAR recommendations for an uninsulated attic: R-49 in climate zones 2 and 3, R-60 in zones 4 through 8, which cover most of the country.

Measure Open-cell Closed-cell
R per inch (aged, settled range) 3.5 to 3.7 6.0 to 7.0
Inches to reach R-49 13.2 to 14 7 to 8.2
Inches to reach R-60 16.2 to 17.1 8.6 to 10
Fits inside a 9.25 inch bay at R-49? No Yes

The depth rows are arithmetic rather than a specification: foam is designed to a thickness by the contractor and sprayed in passes of limited thickness, not ordered in inches from a table. The bay depth row uses 9.25 inches, the dressed depth of a nominal 2x10 under American Softwood Lumber Standard PS 20; framing varies at the eaves and between houses, so measure yours before assuming a bay will take a target. R per inch ranges, their sources, and why the FTC R-value Rule (16 CFR Part 460) makes a product's own label the authority over any generic table, are set out in the method note on the types hub.

The number worth carrying out of that table: for the same R-value, open-cell needs about 1.7 to 1.9 times the thickness of closed-cell, that spread being the two ends of the published R per inch ranges rather than a tolerance. At R-49 it is 13.2 to 14 inches against 7 to 8.2. Between rafters, that difference decides whether the foam fits in the framing or has to be furred down into the room below, and at the eaves, where the rafter meets the top plate, it often decides whether full depth is reachable at all.

The rest of the comparison is behaviour, and behaviour is what actually gets people into trouble. These rows are qualitative on purpose: there is no honest single number for most of them.

Behaviour Open-cell Closed-cell
Vapour permeability Vapour-open. Water vapour moves through it, so in cold climates the assembly design usually adds a vapour retarder on the interior face. Acts as its own vapour retarder at ordinary installed thickness, which is much of why it is specified against a cold roof deck.
Air sealing Air-impermeable once it is thick enough, and thickness is set by the designed R-value rather than by the air sealing. Air-impermeable in a thinner layer, and seals to irregular framing the same way.
Bulk water, meaning a roof leak Water passes through and normally shows as a stain on the ceiling below. The soaked foam then stays wet for a long time. Sheds water. A leak can track along the top of the foam and surface far from its source, or stay hidden while the sheathing takes damage.
Rigidity and framing movement Stays soft, and tolerates seasonal movement in the framing without cracking. Cures rigid and stiffens the assembly, but can crack or lose adhesion where the substrate moves, or was dirty, wet or cold when sprayed.
Airborne sound The softer, open structure absorbs airborne sound better of the two. Rigid and dense. It does comparatively little for airborne sound.
Getting it out later Tears out with hand tools, slowly, and leaves residue on the framing. Comes off by mechanical cutting and scraping. Treat it as permanent.

Read those rows as a pair rather than a scorecard. Closed-cell's vapour tightness is an advantage against a cold deck and a liability in an assembly that needs to dry inward. Open-cell letting water through is a defect while the roof is leaking and a diagnostic advantage afterwards, because you find out. Rigidity buys stiffness and costs you crack tolerance. There is no row where one foam is simply better.

The decision that actually matters: where the insulation plane goes

Almost everyone searching this comparison is standing one step past the decision that determines their outcome. In an attic, the question is not which foam. It is which surface gets insulated: the floor of the attic, or the underside of the roof deck. Those are two different buildings when you are finished, and only one of them involves spray foam at all.

Plane one: the attic floor

Insulation on the floor, ventilation above it. Outside air moves in at the soffit vents, across the underside of the deck and out at the ridge, keeping the roof close to outdoor temperature and carrying away any moisture that gets up there. The attic is outside the thermal boundary of the house and is meant to be. This is how most American houses with pitched roofs are built, it is cheap to improve, and loose-fill blown to depth is the normal material for it. Blowing the floor changes nothing about how the building handles moisture: you are adding depth to a system that already works.

Plane two: the underside of the roof deck

Insulation sprayed against the sheathing, between and often across the rafters. The attic is now inside the thermal boundary. It stays near indoor temperature, ducts and an air handler up there are no longer sitting in a space that swings with the weather, and their leakage and conduction losses land inside the house instead of outside it. This is the conditioned, or unvented, attic, and foam at the roofline is what creates it. That is the real reason spray foam is in the attic conversation at all. It is not that foam is a better blanket than loose-fill. It is that foam is the material that can insulate and air seal a sloped, irregular surface overhead in one pass.

What changes when the plane moves up

Moving the boundary is a change to the physics of the building, not an upgrade to a component. The list below is what a competent contractor will raise before quoting, and its absence from a sales conversation is the clearest signal you are talking to the wrong one.

None of that makes a conditioned attic wrong. Where the duct losses are already landing outside the envelope, moving the boundary is the fix for the actual problem, and the six items above are the scope of work rather than objections to it. What they are not is a material preference to be settled by reading two columns of R-values: the assembly gets designed, and the contractor puts it in writing before anything is sprayed.

How to read a foam quote

Foam is sold by the board foot, meaning one square foot sprayed one inch thick. Because the unit already carries the thickness, board feet per square foot of surface is simply the designed thickness in inches, which makes a quote checkable: reaching R-49 takes 13.2 to 14 board feet of open-cell for every square foot of surface, against 7 to 8.2 of closed-cell, and R-60 takes 16.2 to 17.1 against 8.6 to 10. Multiply by the area actually being sprayed and compare the answer with the board feet on the quote. A quote that gives board feet but no thickness per surface cannot be checked that way, and thin spots are invisible from the hatch once the crew has gone.

What the money turns on:

Installed dollar figures, built up from a measured material price and a stated labour method with its estimates named, are at the cost guide.

Where each one fails

Open-cell

Its failures are moisture failures. It holds bulk water rather than repelling it, so a soaked layer stays wet against wood and takes a long time to give the water back. In a cold climate its vapour openness lets indoor humidity reach cold sheathing, which is the mechanism behind damp or mouldy roof decks in unvented attics that were built vapour-open without an interior retarder. That is a design failure rather than a product failure, and it is repaired by design: a vapour retarder coating on the interior face, or closed-cell against the deck instead. Its other limitation is simple geometry. At 16.2 to 17.1 inches for R-60, it needs depth that many rafter bays do not have.

Closed-cell

Its failures are cost and rigidity. Of the materials this site tracks, it sits at the top of the installed cost ranking per unit of R-value, and the reason is physical rather than commercial: more chemical goes into the same volume than in open-cell, and the work needs a rig, a trained crew and site controls that a bag of loose-fill does not. Sprayed onto framing that moves seasonally, or onto a substrate that was dirty, damp or too cold at the time, it can crack or lose adhesion, and a hairline separation at the rafter edge is an air path you cannot see. Because it sheds water, a leak above it can run a long way before it announces itself. And it buries what it covers: wiring, the top of the deck, and any future roof diagnosis. It is effectively permanent, so treat the decision as permanent.

Both

Which one, given your attic

Find the row that describes your situation and take the recommendation. If two rows apply, the one describing a constraint on the building wins over the one describing a preference.

Your situation Recommendation
Vented attic, open floor you can walk or crawl, no ducts up there Neither foam. Air seal the ceiling plane, then blow loose-fill to your zone's target. See blown-in insulation
Ducts and air handler in the attic, or the attic is finished space Roofline foam, and get the assembly designed. Closed-cell against the deck in cold zones, open-cell where the climate and the design allow it, hybrid assemblies in between
Cathedral ceiling or a roof with no ventilation channel above the insulation Closed-cell. It is the only one of the two that delivers a high R-value and vapour control in the depth available
Roofline job, mild or hot climate, plenty of rafter depth, budget matters Open-cell. Cheaper per inch, and the depth penalty costs you nothing you have to spend
Full depth will not fit at the eaves, but the rest of the floor is fine Closed-cell in that band only, loose-fill everywhere else. Foaming the whole attic to solve a perimeter problem is a large overspend
Roof is near the end of its life Neither, yet. Reroof first, then insulate. Foam sprayed under sheathing that is about to be replaced is money in the skip
Wet, mouldy or rodent-damaged insulation already up there Neither, yet. The attic has to be sound before anything is sprayed or blown into it. Start at the removal guide
Chasing noise reduction from the room below Neither is the efficient fix. If you are foaming the roofline anyway, open-cell has the edge on airborne sound. Do not buy foam for sound alone

If no row moved you off the attic floor, the recommendation is the first row. Air seal, then blow loose-fill to the ENERGY STAR level for your climate zone, and skip both foams. The R-value guide sets your target, and the attic calculator takes your own square footage and current depth and returns what is left to add.

Get quotes from licensed insulation contractors

Tell us the job and your ZIP. We pass it to a licensed contractor who works in your area.

A marketing service, not a licensed contractor. Insulation work is performed by independent licensed local contractors.

When you submit this form, your information is shared with a licensed insulation contractor for the purpose of scheduling your free quote.

By submitting this form, I agree that Compass Camper LLC and an insulation contractor may contact me at the phone number and email I provided, including by automated phone calls, prerecorded messages, and text messages, regarding insulation services. Consent is not a condition of any purchase. Message and data rates may apply. I may opt out at any time by replying STOP to any text or asking to be removed during any call. See our Privacy Policy.

You may not need either

We do not sell insulation and we do not install it, which is why this section can say what it says. Most people who arrive comparing open-cell against closed-cell should buy neither.

For a standard vented attic with a floor you can reach, loose-fill blown to the target depth costs a fraction of foam and holds heat identically. R-49 is R-49: a ceiling insulated to R-49 with blown fibreglass or cellulose, made to specifications such as ASTM C739 in the case of cellulose, resists conducted heat the same as a ceiling insulated to R-49 with foam. There is no premium performance hiding inside the expensive material. What foam actually buys on a floor is air sealing, and that is work you can buy on its own for far less: canned foam, caulk and rigid material around the top plates, recessed lights, plumbing stacks, wire penetrations and the hatch, done before the loose-fill goes over it. DOE guidance treats sealing the ceiling plane as the partner job to insulating it, and on a leaky ceiling it is the better first spend either way.

Two more cases where the answer is to spend nothing this year. If you are already within about R-10 of your zone's recommendation, more depth pays back slowly. That R-10 threshold is an estimate rather than a measurement, set at roughly one step of the ENERGY STAR table. Measure what you have before shopping: the depth checker turns inches into an R-value range. And if the attic is dry, clean and simply thin, the cheapest correct job is more of whatever is already there, not a different material over the top of it.

Related

Common questions

Which is better in an attic, open-cell or closed-cell spray foam?
Neither is better in general, and in most attics neither is the right answer. Closed-cell carries about R-6.0 to R-7.0 per inch against open-cell at about R-3.5 to R-3.7, so it reaches a target in roughly half the thickness and it acts as its own vapour retarder. Open-cell costs less per inch, stays flexible as framing moves, and lets water through rather than hiding it. The question that decides more than the material is whether the insulation belongs on the attic floor or on the underside of the roof deck, because that changes how the roof dries.
How many inches of spray foam does R-49 take?
From the R per inch ranges this site carries, R-49 takes about 13.2 to 14 inches of open-cell foam or about 7 to 8.2 inches of closed-cell. R-60, the ENERGY STAR level for an uninsulated attic in climate zones 4 through 8, takes about 16.2 to 17.1 inches of open-cell or 8.6 to 10 inches of closed-cell. Those are arithmetic on published ranges, not a specification. Foam is not ordered in inches from a table: the contractor designs a thickness for the assembly and sprays it in passes, and the quote should state that thickness and the target R-value for every surface.
Does foaming the attic mean closing the soffit and ridge vents?
If the foam goes on the underside of the roof deck, usually yes. A vented attic works by moving outside air through soffit and ridge vents. Insulating the deck moves the thermal and air boundary up to the roof, which brings the attic inside the conditioned house, and leaving the vents open would then pump outside air into insulated space. Closing them changes how the roof sheathing dries, which is why an unvented attic is treated as a designed assembly rather than a preference. Have the contractor state in writing which vents close and what replaces them.
Will spray foam hide a roof leak?
It can, and the two foams fail differently. Water passes through open-cell foam, so a leak usually shows as a stain on the ceiling below, although the soaked foam then stays wet. Closed-cell sheds water, so a leak can travel along the top of the foam and appear far from its source, or stay out of sight while the sheathing takes damage. Neither is a reason to rule foam out. Both are reasons to replace a roof that is near the end of its life before anything is sprayed to the underside of its deck.
Can I install spray foam myself?
Not at attic scale. Spray polyurethane foam is a two-part chemical reaction with mixing ratios, hose and substrate temperature requirements and a limit on how thick each pass can be. Off-ratio foam can shrink, smell or never fully cure, and the only remedy is cutting it out. The chemistry is isocyanate-based, which the EPA, the CDC and NIOSH all publish exposure guidance on, and crews work in respiratory protection under OSHA rules with the house vacated during and after spraying. The small kits sold for sealing gaps are a different product from an attic job.
Does closed-cell foam need a separate vapour barrier?
Usually not an added one. Closed-cell at ordinary installed thickness acts as its own vapour retarder, which is a large part of why it is specified against a roof deck in cold climates. Open-cell is vapour-open, and in colder zones the design often adds a vapour retarder coating on the interior face instead. Which applies to your house depends on the climate zone and on the rest of the assembly, so it is a question for the contractor and your building department rather than for a national table. Get the answer in writing before the rig arrives.
What should a spray foam quote state?
Thickness in inches and target R-value for every surface sprayed, the product and its blowing agent, the area in square feet of the roof plane rather than the attic floor, which vents are being closed and what replaces them, how the foam will be covered to satisfy the ignition or thermal barrier rules your building department enforces, how long the house has to be vacated, and what happens to the insulation already lying on the attic floor. A quote carrying one number and no thickness cannot be compared with anything.